Telecom Inverter

Telecom Inverter

Description

The most common application of direct to alternating current converter is in UPS (Uninterrupted Power Supply), which converts the battery power to 230 V or any other desired alternating voltage when there is a lack of city electricity. The conversion process here can also be done using linear or switch mode technology. In linear technology, DC voltage is first converted to AC voltage, then it is returned to alternating voltage with a certain range using a transformer and filter. In the switch mode method, the same work is done at high frequencies and using high frequency transformers.

Specifications of inverters:

  • DC input: 24, 48, 110, and 220 volts
  • AC output: 230 V or according to the order and requirement
  • Output power: usually up to 30 kVA; Greater powers by order
  • Output power 1KVA 2KVA 3KVA 4KVA 5KVA 6KVA 7KVA 8KVA 9KVA 10KVA
    Run mode Pure inverter/online interactive
    DC Input Rated input voltage 24V/48V 48V
    Rated input current(A) 50/ 24 100/48 150/72 200/96 119 125 143 167 214 238
    Turn-off voltage range 24Vdc(20V-30V)   48Vdc(42V-59V)
    Turn-on voltage range 24Vdc(22V-28V)   48Vdc(45V-57V)
    Anti-noise current irrigation ≤10%
    AC Input Bypass voltage 265V-185V(±10V)
    Rated input current
    (A)
    5٫4 10٫8 16٫2 21٫6 22٫7 27 37٫8 36٫4 43٫2 54
    Bypass transfer time
    (ms)
    ≤5ms
    AC output Power factor 0٫8 0٫7
    Rated capacity
    (VA)
    1K 2K 3K 4K 5K 6K 7K 8K 9K 10K
    Rated output power 800W 1600W 2400W 3200W 3500W 4200W 4900W 5600W 6300W 7000W
    Rated output voltage and
    frequency
    220Vac, 50Hz
    Wave shape Pure sine wave
    Rated output current 3٫6A 7٫2A 10٫9A 14٫5A 16A 19٫1A 22٫3A 25٫5A 28٫6A 31٫8A
    Output voltage
    accuracy
    220V±1%
    Output frequency accuracy 50Hz±0٫1%
    Waveform distortion ≤3%
    Dynamic Response Time 0٫05
    Overload 120%, 30s
    Inverter efficiency
    (80% Resistive load)
    ≥85%
    Work condition Dielectric Strength input & output 1500Vac, 1min
    Noise
    (1m)
    ≤40dB
    Ambient temperature -25℃~+50℃
    Humidity 0~95%, Non-condensing
    -Altitude-M ≤1500
    Cooling Forced air
    Interface HMI LCD+LED display
    Communication interface RS232/RS485/RJ45(Choose one)
    dry contact load output 2ch /3ch output ( Choose one)
    TCP/IP network interface Optional
    Protection  Input under/over voltage; output overload, short circuit protection;AC input high and
     low voltage protection
    Output wiring Sockets and terminals Terminal Blocks